| Output: Voltage and Current Ranges |
|
| Model |
CW 801M |
CW 1251M |
CW 2501M |
CW 801P |
CW 1251P |
CW 2501P |
| Power |
800VA |
1250VA |
2500VA |
800VA |
1250VA |
2500VA |
| Voltage |
| Voltage Range |
0 to 135Vrms, 0 to 270Vrms, user selectable |
| Accuracy (>5VAC) |
±1% of Range |
±0.1% of Range <100Hz ±0.2% of Range > 100Hz |
| Resolution |
0.1 Vrms |
| Total harmonic distortion |
0.25% typical <100Hz add 0.5%/100Hz above 100Hz |
| AC noise level (typical) |
<50
mVRMS |
<50
mVRMS |
<100
mVRMS |
<50
mVRMS |
<50
mVRMS |
<100
mVRMS |
| Amplitude stability1 |
±0.1% of full scale |
±0.05% of full scale |
| Load regulation |
±0.1% of full scale voltage for a full resistive load to no load (<10 mVRMS typical, measured at point of sense) |
| Line regulation |
±0.1% of full scale voltage for a ±10% line change from nominal line voltage
(<5 mVRMS typical, measured at point of sense) |
| Remote voltage sense |
5 Vrms total lead voltage drop |
| Current |
| 135VAC Range |
6.0 ARMS |
9.4 ARMS |
18.6 ARMS |
6.0 ARMS |
9.4 ARMS |
18.6 ARMS |
| 270VAC Range |
3.0 ARMS |
4.7 ARMS |
9.3 ARMS |
3.0 ARMS |
4.7 ARMS |
9.3 ARMS |
| Accuracy |
± 0.5% typical |
± 0.5% max |
| Resolution |
0.1 ARMS |
0.01 ARMS |
| Frequency Range |
| Range |
45 to 500 Hz |
45 to 500 Hz, 45 to
1000 Hz (option) |
| Accuracy |
±0.5% typical |
±0.02% max |
| Resolution |
0.1 Hz |
0.1 Hz, 0.01 Hz for
remote programming |
| Phase |
All models single phase output. Multi-phase system configuration with Digital Expansion Cable |
| Power Factor of Load |
0 lag to 0 lead |
|
 |
|
 |
|
| Model |
CW 801M |
CW 1251M |
CW 2501M |
CW 801P |
CW 1251P |
CW 2501P |
| Power |
800VA |
1250VA |
2500VA |
800VA |
1250VA |
2500VA |
| Voltage |
| Range |
0 to 270 Vrms |
0 to 270 Vrms, 0 to
310VRMS (option) |
| Accuracy2 (VAC>5V) |
± 1% of full range |
±0.1% of range <100 Hz, ± 0.2%
of range>100 Hz,
± 0.3% of range>500 Hz (option) |
| Resolution |
0.1 Vrms |
0.1 Vrms |
| Current3 |
| 135VAC Range |
6.0 ARMS |
9.4 ARMS |
18.6 ARMS |
6.0 ARMS |
9.4 ARMS |
18.6 ARMS |
| Accuracy |
±2% of range for linear loads
with current >0.2A,
> 0.4A for 2500 VA |
±0.5% of range for linear loads |
| Resolution |
0.1 ARMS |
0.01 ARMS |
| Peak Current3 |
| Range |
- |
- |
- |
0 to 25A |
0 to 35A |
0 to 70A |
| Accuracy |
- |
- |
- |
±1% of Range |
| Resolution |
- |
- |
- |
0.1A |
| Frequency |
| Range |
45 to 500 Hz |
45 to 500 Hz, 45-1 000 Hz (option) |
| Accurace |
± 0.5% of reading |
± 0.02% of value |
| Resolution of display |
0.1 Hz |
0.1 Hz |
|
 |
|
 |
|
| Model |
CW 801P |
CW 1251P |
CW 2501P |
| Power |
800 VA |
1250 VA |
2500 VA |
| Power3 |
| Range |
0 to 800W |
0 to 1250W |
0 to 2500W |
| Accuracy |
±2% of range for linear loads |
| Resolution |
1W |
| Apparent Power3 |
| Range |
0 to 800 VA |
0 to 1250 VA |
0 to 2500 VA |
| Accuracy |
±2% of range for linear loads |
| Resolution |
1 VA |
| Power Factor3 |
| Range |
0 to 1 |
| Accuracy |
±4% of range for linear loads |
| Resolution |
0.01 |
| Crest Factor |
| Range |
0 to 3.5 |
| Accuracy |
±5% of range |
| Resolution |
0.01 |
| Phase |
| Range |
-359 to +359 degrees.
Positive indicates time lag from reference |
| Accuracy |
Within 100 microseconds of equivalent angle |
| Resolution |
1 degree |
|
 |
|
 |
|
| Model |
CW 801M |
CW 1251M |
CW 2501M |
CW 801P |
CW 1251P |
CW 2501P |
| Power |
800VA |
1250VA |
2500VA |
800VA |
1250VA |
2500VA |
| Voltage |
90 to 264 VAC |
103 to 264 VAC |
180 to 264 VAC |
90 to 264 VAC |
103 to 264 VAC |
180 to 264 VAC |
| Current |
13 ARMS max |
18.5 ARMS max |
19.5 ARMS max |
13 ARMS max |
18.5 ARMS max |
19.5 ARMS max |
| Frequency |
47 to 63 Hz |
| Phases |
single-phase |
| Power Factor |
>0.99 typical at full load nominal line |
| Efficiency |
>73% typical at full load |
|
 |
|
 |
|
| Model |
CW 801M |
CW 1251M |
CW 2501M |
CW 801P |
CW 1251P |
CW 2501P |
| Dimensions |
19 W x
5.216 H x
20.07 D |
19 W x
5.216 H x
20.07 D |
19 W x
5.216 H x
20.07 D |
19 W x
5.216 H x
20.07 D |
19 W x
5.216 H x
20.07 D |
19 W x
5.216 H x
20.07 D |
| Weight |
48Lbs (22kg) |
53Lbs (24kg) |
86Lbs (39kg) |
48Lbs (22kg) |
53Lbs (24kg) |
86Lbs (39kg) |
| Shipping Weight |
56Lbs (25kg) |
61Lbs (28kg) |
94Lbs (43kg) |
56Lbs (25kg) |
61Lbs (28kg) |
94Lbs (43kg) |
|
 |
|
 |
|
| Front Panel Indicators |
Displays & indicators menu/status
Enter/escape buttons are present for programming
Voltage mode (volts, watts, VA, PF)
Green LED
Measure (amps, Hz, Pk amps, CF)
Green LED
Program (amps, Hz I Limit) Green LED
Voltage range high/low
Green LED |
| Regulatory compliance |
CE mark, UL and CUL (consult factory for
availability) |
|
 |
|
 |
|
| Cooling |
Dual fan speed with side air intake, exhaust to
rear
|
| Operating temperature |
0 to 40°C
|
| Storage temperature |
-40 to +70°C
|
| Humidity |
0 to 85% at 25°C derate to 50% at 40°C (non
condensing)
|
| Altitude |
Operating full power available up to 6,000 feet,
non operating to 40,000 feet |
|
 |
|
 |
|
 |
|

|
 |
 |