Input
Input Voltage, AC: 85 to 140 VAC or 170 to 280 VAC
Single Phase
Input
Current, AC: 33A at 120 VAC, 17A at 240 VAC
Input Frequency, AC: 45 to 450 Hz
Input
Voltage, DC (GUPS 2400AD only): 20 to 32 VDC
Internal
Battery Module: 192 VDC, 2.5 AH. Optional external battery packs
available
Battery
Hold-Up Time: 5 minutes for internal module with
2400 VA load, 0.8 PF @ 25°C. Adding one external battery pack increases
time to a minimum of 18 minutes at full rated load. Reduced loads increase
backup time.
Input
Current DC (GUPS 2400AD only): 105A at 28 VDC
GUPS
2400AD: 10 minutes for external battery chassis with 2400 VA load,
0.8 PF at 25°C. Adding additional external battery packs increases backup
time.
Environmental
Altitude: Operating 0 to 10,000 ft; non-operating 0 to 40,000 ft
Temperature: Operating 0° to 40°C; non-operating -40° to 65°C
Humidity: 5 to 95% non-condensing
General
Weight
GUPS 2400A: 78 lbs, maximum without battery module. Removable internal
battery module is 48 lbs (126 lbs max combined weight). GUPS 2400A-104
variant (123 lbs max combined weight).
Weight GUPS 2400U: 83 lbs, maximum without battery module. Removable
internal battery module is 48 lbs (131 lbs max combined weight).
Weight GUPS 2400AD: Main chassis is 95 lbs; battery chassis 116
lbs, total weight 211 lbs.
Dimensions: 7"H x 19"W x 21"L (GUPS 2400AD two chassis)
7"H x 19"W x 25.1"L (GUPS 2400A-104)
Internal
Battery Module
Battery
Description (GUPS 2400A and GUPS 2400U): 192 VDC, 2.5 AH sealed
lead acid
Configuration: 96 cells at 2.0 V, 2.5 AH in a single pullout, removable module
Recharge
Time: 4 hours, 90% full charge with integral battery charger
Typical
Minimum Hold-Up Time 2400 VA at 25°C: 5 minutes
Microprocessor
Controlled Equalization: Batteries maintained on a temperature compensated,
constant voltage float charge with automatic equalization as required
Temperature: Operating 0° to 40°C; non-operating -40° to 65°C
Weight
of Removable Module: 48 lbs
External Battery Chassis for GUPS 2400AD
Battery
Description:
192 VDC, 5 AH sealed lead acid
Configuration:
Two modules, 2.5 AH each
Recharge
Time:
6 hours, 90% full charge with integral battery charger
Typical Minimum Hold-Up Time 2400 VA at 25°C:
10 minutes
Temperature:
Operating 0° to 40°C, non-operating -40° to 65°C
Alarms and Signals
Alarms:
The audible alarm sounds for an overtemperature, loss of AC input
or improper battery voltage.
Signals:
(1) Isolated relay contacts signal loss of AC input and impending
inverter shutdown due to low battery capacity and
(2) RS 232 data communications
for computer interface provides information on GUPS status, alarms and
parameter values.
Indicators
AC Input: A three color LED indicates the condition of the AC input
voltage. The LED is green when the AC input voltage is within the normal
operating limits, amber when the voltage is close to the limits of the
operating range and red when the operating voltage range is exceeded.
Battery:
A three color LED indicates the condition of the battery.
The LED is green under normal operating conditions, amber when the battery
is discharging or has low capacity and red when impending inverter shutdown
is approached.
Load:
A three color LED indicates the amount of output load.
The LED is
green when the load is less than 80% of maximum output, amber when the
load is within 80% to 105% and red when the load exceeds 105%, indicating
that the inverter will shut down if the load is maintained.
Temperature:
A two color LED indicates the overtemperature condition
of the GUPS.
The LED is green under normal operating conditions and
red when an over- temperature occurs.
Test:
A two color LED indicates the results of the internal self-test.
A blinking light indicates the test is in progress.
When the test is
complete, the LED turns green if the GUPS passes the test and red if
it fails.
Controls
Output On:
Switches on or off the GUPS output
Test:
Initiates the internal self-test
Alarm
Silence:
Silences the audible alarm
Remote Shutdown (GUPS 2400U only):
Switches off the UPS output and disconnects
the UPS from the AC input source.
Requires external SPST contact closure
Frequency Switch
Output Frequency (GUPS 2400U only): Selects 50 or 60 Hz output
Configuration Terminal Block
Output Voltage (GUPS 2400U only): Selects 115 VAC or 230 output
|