Electrical Specifications 1

 

Output Ratings:

 

 

 

Output Voltage

 

0-15 V

 

Output Current

 

0-20 A

 

Output Power

 

300 W

 

Line Regulation: 2

 

 

 

Voltage (0.01% of Vmax + 2 mV)

 

2 mV

 

Current (0.01% of Imax + 1 mA)

 

3 mA

 

Load Regulation: 3

 

 

 

Voltage (0.01% of Vmax + 2 mV)

 

2 mV

 

Current (0.01% of Imax + 5 mA)

 

3 mA

 

Meter Accuracy:

 

 

 

Voltage (1% of Vmax + 1 count)

 

0.25 V

 

Current (1% of Imax + 1 count)

 

0.3 A

 

Output Noise & Ripple:

 

 

 

Voltage rms

 

5 mV

 

Voltage (p-p) (0-20 MHz)

 

75 mV

 

Drift (8 hours): 4

 

 

 

Voltage (0.02% of Vmax)

 

3 mV

 

Current (0.03% of Imax)

 

6 mA

 

Temperature coefficient: 5

 

 

 

Voltage (0.015% of Vmax/° C)

 

2.25 mV

 

Current (0.02% of Imax/° C)

 

4 mA

 

Interface Specifications 1,6

 

Program Resolution (16-bit):

 

 

 

Voltage

 

0.25 mV

 

Current

 

0.34 mA

 

OVP

 

0.25 mV

 

Program Accuracy:

 

 

 

Voltage (0.2% + 10 mV)

 

60 mV (+/- 0.1%)

 

Current (0.3% + 10 mA)

 

75 mA (+/- 0.12%)

 

OVP (0.5%) + 100 mV)

 

1500 mV

 

Readback Resolution (16-bit):

 

 

 

Voltage

 

0.25 mV

 

Current

 

0.34 mA

 

Readback Accuracy:

 

 

 

Voltage (0.2% + 20 mV)

 

45 mV (+/- 0.3%)

 

Current (0.3% + 20 mA)

 

75 mA (+/- 0.12%)

 

 

 

 

 

1. Specifications indicate typical performance at 25° C +/- 5° C, nominal line input of 120 VAC.

 

2. For input voltage variation over the AC input voltage range, with constant rated load.

 

3. For 0-100% load variation, with constant nominal line voltage.

 

4. Maximum drift over 8 hours with constant line, load and temperature, after 60 minutes warm-up.

 

5. Change in output per ° C change in ambient temperature, with constant line and load.

 

6. Apply accuracy specifications according to the following voltage program accuracy example:
    Set a model 15-20 power supply to 10 volts. The expected result will be within the range of
    10 volts +/- 60 mV +/- 0.1% of the set voltage of 10 volts.

 

 

General Specifications

 

Operational AC input voltage

 

Single unit: 104-127 VAC at 6 Arms; Dual unit: 104-127 VAC at 12 Arms, 47-63 Hz

 

Switching Frequency

 

100 kHz (nominal)

 

Voltage Mode Transient Response Time

 

<500 µs recovery to 50 mV band for ±50% load change in the range of 25% to 100% of the rated load

 

Operating Ambient Temperature

 

0 to 30° C for full rated output. Above 30°C, derate output linearly to zero at 70° C

 

Storage Temperature Range

 

-55° C to 85° C

 

Humidity Range

 

0 to 80% RH, non-condensing

 

Front Panel Voltage and Current Control

 

10-turn voltage and 1-turn current potentiometers (10-turn current optional)

 

Front Panel Voltage Control Resolution

 

0.02% of maximum voltage

 

AC Input Connector Type

 

IEC 320 connector

 

Weight (one unit)

 

Approximately 7.7 lb (3.5 kg)

 

Dimensions (H x W x D)

 

5.2 x 4.2 x 11.7” (132 x 109.2 x 297 mm)

 

Options

 

GPIB-HPD

 

GPIB Interface card (16-bit)

 

RS-232-HPD

 

RS-232 Interface card (16-bit)

 

APG-HPD

 

Analog programming interface card

 

M2

 

200-250 VAC Input (50/60 Hz)

 

M2S

 

Switch selectable input 110 VAC or 220 VAC

 

M11

 

10-turn current potentiometer

 

M13 A

 

Locking knobs for front panel controls

 

RM-XHS

 

19-inch rack mount kit for up to four HPD, XPD or XT power supplies

 

Analog Programming

 

Remote On/Off and Interlock

 

2-25 VDC high. <0.8 VDC low. User-selectable.

 

Remote analog Programming Option

 

0-10 VDC for 0-100% of rated voltage or current ±1.0%, 0-10 kΩ for 0-100% of rated voltage or current ±1.0%

 

Remote Monitoring

 

0-10 VDC for 0-100% or rated voltage or current ±1.0%

 

Over Voltage Protection Trip Range

 

3 V to full output ±10%

 

Tracking Accuracy

 

±1% for series operation

 

Regulatory Approvals

 

CE-marked units meet: EN61010-1, EN61000-6-2 and EN61000-6-4; CSA C/US certified to UL61010-1B and CSA C22.2 No 1010.1; Meets USA EMC standard: FCC, part 15B, class A; Meets Canadian EMC standard: ICES-001, Class A.

 

Note: Specifications subject to change without notice.