LHP Series : Specifications
Output Voltage and Current
Model Voltage Current
LHP 7.5-130 0-7.5 0-130
LHP 20-50 0-20 0-50
LHP 33-33 0-33 0-33
LHP 40-25 0-40 0-25
LHP 60-18 0-60 0-18
LHP 100-10 0-100 0-10
LHP 150-7 0-150 0-7
LHP 300-3.5 0-300 0-3.5
LHP 600-1.7 0-600 0-1.7
Common
Operating Temperature 0 to 40°C
Storage Temperature -40°C to 85°C
Humidity 0-80% RH, non condensing
Cooling Forced air
Front Panel Control 10-turn voltage and current potentiometers
Front Panel Voltage Control Resolution 0.02% of voltage maximum
Main Output Nickel plated copper bus bars for models up to 40V. Wire clamp connector for models over 40V (30A max from front panel) Remote Start/Stop and Interlock: TTL compatible input, selectable logic
Meter Accuracy 1% of full scale + 1 count Adjustable OVP: OVP range 5% to 110% of V max
Remote Sense Voltage

5V maximum drop per line (3V/line for LHP 7.5-130). Line drop subtracts from the maximum available output voltage at full rated power.

Maximum Voltage Differential (output to safety ground) 600 VDC
Transient Response (Voltage) 1 ms for output voltage to recover within 0.1% of previous level
after step change in load current of up to 50% of rated output
Stability 0.05% of maximum voltage over 8 hours after 60 minute warm up time at fixed line, load and temperature
Efficiency 80% typical. Typical efficiency at 115 VAC input and rated output power.
Temperature Coefficient See table on the next page. Change in output per °C change in ambient temperature, with constant line and load.
Regulatory Compliance CE Mark
Physical
Dimensions 2U or 3.50” (88 mm) H x
8.45” (214 mm) Wt x
18.60” (472 mm) D
Weight 18 lbs. (8.2 kg)
Shipping Weight 20 lbs. (9 kg)
Input
Voltage and Frequency 85-250 VAC, 47-63 Hz
Connector IEC 320 15A/250V
Current 13A max at 100 VAC, 11A max at 120 VAC, 6A max at 220 VAC
Power Factor 0.98 minimum for full load
Input Harmonic Distortion Current harmonics meet IEC555-2 limits
Investigate our discount web specials
  Product Configurator  
DC Electronic Loads
DC Modular Supply
Discontinued Products
Product Support
Contact Sales

Noise and Ripple
Output Power
Line Regulation
Output Power
Load Regulation
Output Power
M5A: J-305 Pin Assignments
1 Overvoltage Protection Flag 14 Not Used
2 TTL Shutdown Return 15 TTL Shutdown
3 Not Used 16 Current Limit Program
4 Program Return 17 Voltage Program
5 Program Return 18 Current Readback
6 Auxiliary Ground 19 Voltage Readback
7 Remote Voltage Program Select 20 +10V Reference Out (10 mA max.)
8 Remote Current Program Select 21 Output Fail Flag
9 Voltage Current Limit Mode Indicator 22 + Sense
10 + Out 23 + Out
11 + Out 24 - Return
12 - Return 25 - Sense
13 - Return