ELECTRICAL CHARACTERISTICS
- Control Mode
Current Control
- Front Panel Meter Accuracy
Voltage ±0.5% of full-scale + 1 digit
Current ±0.5% of full-scale + 1 digit
- Load Regulation
(no load to full load, nominal AC input)
Current 0.1% of rated output current
- Line Regulation
(±10% of nominal AC input)
Current 0.05% of rated output current
- Current Ripple
1% p-p of full-scale current
- Transient Response
Output current recovers to within 1% of current setpoint within 1ms for a 10 to 100% or 100% to 10% step load change
- Output Slew Rate
250A/ms rise, 200A/ms fall at full load (minimum)
400A/ms typical
Current Overshoot
Maximum 8% of full-scale for 0 to 100% change into a resistive load
- Output Capacitance
60V Models: <2µF
160V Models: <3µF
- Stability
±0.05% of setpoint after 8–hr. warm-up at fixed line, load, and temperature using remote sense
- Power Factor
>0.9 typical for 208/220VAC input
>0.78 typical for 380/400VAC input
>0.7 typical for 440/480VAC input
- Remote Analog Control
Current Setpoint Accuracy
±0.8% of full-scale output
- Overcurrent Protection
±1% of full-scale output
- Resistive Control
0–5 kW = 0-100% Current
- Voltage Control
0–5 or 0–10 VDC = 0-100% Current
- Overcurrent Protection
0–5.5 VDC = 0-110%
- Efficiency
87% typical at full load, nominal line
- Remote Control/Monitor
On/Off control via contact closure, 6-120 VDC or 12-240VAC, and TTL or CMOS switch, current monitor, OCP limit set, summary fault status
- Overvoltage Protection
Fixed at approximately 110% of the rating compliance voltage. Reset requires cycling the front panel standby power switch off/on
Isolated Analog Control (option)
Input to Output Isolation: 500 V
Compliant with maximum terminal float voltage.
Recommended operation under SELV normal conditions.
ENVIRONMENTAL CHARACTERISTICS
- Ambient Operating Temperature
0 to 50°C
- Storage Temperature
-25 to 65°C
- Temperature Coefficient
Current Setpoint
0.03%/°C of rated current
- Cooling
Internal Fans. Zero clearance stacking
- Humidity
0 to 90% at 40°C; 0 to 50% at 25°C
non-condensing
- Altitude
Full power at 5,000 feet, 10% derating of full power for every 1,000 feet above 5,000 feet
- Regulatory
Certified to UL/CSA 61010 and IEC/EN 61010-1
CE Compliant (LVD and EMC Directives)
INPUT POWER OPTIONS
- Configuration
3–phase, 3–wire plus ground. Not phase rotation sensitive. Neutral not used.
- Voltage Selection
208/220 VAC±10%, 47 to 63 Hz
380/400 VAC±10%, 47 to 63 Hz
440/480 VAC±10%, 47 to 63 Hz
PHYSICAL
- Up to 15kW in 3U
19.00in W x 25.12in D x 5.25inH; 80 lbs.
(48.3cm W x 63.8cm D x 13.3cm H; 36 kg)
- 15 - 30kW in 6U
19.00in W x 25.12in Dx 10.5in x H; 160 lbs.
(48.3cm W x 63.8cm D x 36.7cm H; 73 kg)
|
 |
|

|
 |
 |