| Output Ripple (p-p, 20 MHz) |
|
| Voltage |
80 mV |
| Maximum Recommended Remote Sense Line Drop Compensation per Line9 |
5 V |
| Up-prog. Response Time, 0~Vmax10 |
100 ms |
| Down-prog. Response Time: Full Load |
100 ms |
| Down-prog. Response Time: No Load |
1200 ms |
| Over-Voltage Trip Point |
3–125 V |
| Efficiency11 |
83/87% |
|
 |
|
 |
1. |
Maximum output voltage is guaranteed to be 0.1% of the rated voltage at zero
output setting, using the front panel or digital remote programming modes. |
 |
| 2. |
Maximum output current is guaranteed to be 0.2% of the rated current at zero output setting, using the front panel or digital remote programming modes, and when measured with rated load resistance. |
 |
| 3. |
Total output power is also based on AUX1 Output Voltage (5 V) and AUX1 Output Current (0.5 A) and AUX2 Output Voltage (15 V) and AUX2 Output Current (0.5 A). |
 |
| 4. |
From 85–132 Vac or 170–265 Vac, constant load. |
 |
| 5. |
From 85–132 Vac or 170–265 Vac, constant load. |
 |
| 6. |
From no load to full load, constant input voltage. |
 |
| 7. |
For load voltage change, equal to the unit voltage rating, constant input voltage. |
 |
| 8. |
For 6 V models the current ripple is measured at 2–6 V output voltage and full output current. For all other models, the current ripple is measured at 10–100% output voltage and full output current. |
 |
| 9. |
When using remote sense, the total of the load voltage and the load line drops must not exceed the rated output of the power supply. For example, for an XTR 6-110 in an application with 1 V of
load line loss (0.5 V/Line), the maximum available load voltage would be 6–1= 5 V. Note: The unit may operate at higher output voltages than this, but there is no guarantee that the power supply
will meet performance specifications. Ultimately, the upper limit of the output voltage will be determined by internal circuitry of the power supply (non-adjustable.) |
 |
| 10. |
With rated, resistive load. |
 |
| 11. |
At 100/200 Vac input voltage and maximum output power.
Applies to all footnotes: Programming and Readback: RS-232, RS-485, USB built in. GPIB, Ethernet optional. |
 |
| Specifications are guaranteed from 1% to 100% of the rated
output voltage, current, and power. |
 |
| Environmental Specifications (Indoor use) |
|
| Operating Temperature Range |
32°F to 122°F, 100% load (0°C to 50°C) |
| Storage Temperature Range |
-4°F to 158°F (–20° C to 70°C) |
| Operating Humidity Range |
30–90% RH (no condensation) |
| Storage Humidity Range |
10–95% RH (no condensation) |
| Operating Altitude |
Up to 6,500 feet (2,000 m) |
| Installation Category |
II (IEC 1010-1) |
| Pollution Degree |
2 (IEC 1010-1) |
|
 |
|
 |
|
| Safety |
CSA 22.2 No. 61010-1 and UL61010-1. Marked with c(UL) us, CE EN61010-1 |
| EMC |
Complies with EN55022, Class B, FCC Part 15B for conducted emissions,
Complies with EN55022, Class A, FCC Part 15A for radiated emissions,
Complies with EN61000-4 series of standards for immunity |
| Warranty |
Five Years |
|
 |
|
 |
| Programming Mode |
APG |
ISOL |
Digital |
|
| Voltage & Current Output Voltage Programming |
0-100% Voltage control range is 0.0 to 2.0 - 10.0V in 0.1V increments |
|
| Voltage & Current Output Resistive Programming |
0-100% Resistive control range is 0.0 to 2.0 - 10.0V in 0.1V increments |
|
| Output Voltage and Current Monitor |
0-100% Output Voltage Monitor range is 0.0 to 2.0 - 10.0V in 0.1V increments |
|
| Voltage Programming Accuracy1 |
± 0.5% of rated output voltage, max (0 to 4.0V / 4K Ohm range)
± 0.5% of rated output voltage, typical in other ranges |
± 0.1% of rated output voltage |
| Current Programming Accuracy1 |
± 0.5% of rated output current, max (0 to 4.0V / 4K Ohm range)
± 0.5% of rated output current, typical in other ranges |
± 0.2% of rated output current6 |
| Voltage Feedback Accuracy |
± 1% of rated output voltage |
± 0.1% of rated output voltage |
| Current Feedback Accuracy |
± 1% of rated output current |
± 0.2% of rated output current |
| Isolation (Prog and Readback Lines) |
With respect to chassis potential: 500 V |
With respect to:
chassis potential: 500 V
negative or positive main output 1500 V
negative or positive auxiliary output 300 V |
|
| Parallel Operation |
Up to 4 units in master slave mode |
|
|
| Series Operation |
Up to 2 units (with external diodes) |
|
|
| Constant Voltage (CV) Constant Current (CC) Indicator |
CV: TTL High (4-5 V)
CC TTL Low (0-0.6 V) |
|
|
| Shutdown Control2 |
|
Logic low 0.0 - 1.4 V
Logic high 2.0 - 15 V
Dry contact compatible |
|
| AUX On/Off Control |
|
TTL level or dry contact compatible |
|
| Power Supply Status Signal |
|
TTL high: OK (4-5 V)
TTL low: fail (0-0.6 V) |
|
| Interlock Enable/Disable |
|
Dry contact. Open/Short: On or
Off programmable |
|
|
 |
|
 |
| 1. |
Typical APG or isolated APG accuracy can be improved to max accuracy by user calibration at the specific range selected |
 |
| 2. |
The shutdown input has user selectable negative logic operation via front panel or remote digital input/output |
 |
| AC Line Input Specifications |
|
| Rated AC Input Voltage/Frequency |
100–240 Vac, 47–63 Hz |
| Operational AC Input Voltage/Frequency |
85–265 Vac continuous, 47–63 Hz, single phase |
| Input Current (at 100/200 Vac) |
11.5/6 A (850 W) |
| Inrush Current (100/200 Vac) |
Less than: 25 A (850 W) |
| Power Factor Correction |
0.99@100/200 Vac, rated output power |
|
 |
|
 |
| Output Performance Specifications |
|
| Temperature Coefficient |
100 PPM/° C from rated output voltage, after a 30-minute warm-up |
| Drift (8 hours) |
0.05% of rated output voltage & current over an 8 hour interval with constant line, load & temperature, after a 30-minute warm-up |
| Hold-up Time |
Typical 20 ms at any rated input line. |
| Transient Response Time2 |
Less than 1 ms for 6 V to 60 V models. Less than 2 ms for 80 V to 600 V models |
| Meter Accuracy |
0.5% of actual output voltage or current ± 1 count |
| Aux output1 |
+5 V: +0.4 V, – 0.5 V at 0.4 A
+15 V: +1.2 V, – 1.4 V at 0.4 A |
| Isolation |
AC Input to Output
AC Input to Chassis
Output to Chassis3 |
1350 Vac
1350 Vac
500 Vac |
|
 |
|
 |
| 1. |
Current: 0.51 A minimum guaranteed, 0.72 A typically available. Overcurrent protection (each output) is automatic, non-latching. When OCP is tripped the aux voltage folds back and will recover to nominal condition when the over current condition is removed (typ. <0.2A).
To protect external circuits attached to the aux outputs it is recommended that customers use an appropriately rated fuse in series with the aux outputs set point 10-100% |
 |
| 2. |
Time for the output voltage to recover within 0.5% at its rated output for a load change 10-90% of rated output current. Output set point 10-100% |
 |
| 3. |
For floating chassis ground applications, please contact application engineering for system design assistance. |
 |
| Mechanical Specifications |
|
| XG 850 Watt (W×H×D) |
8.4 × 1.7 × 19.0 inch (214 × 43.6 × 483 mm) |
| Weight 11 lb (5kg) |
| Cooling Forced air cooling by internal fans |
|
 |
|
 |
|